Uninterruptible Power Supply (UPS)

An uninterruptible power supply (UPS) keeps connected equipment running from batteries or other stored energy when the mains supply fails or its voltage suddenly drops. Fabs depend on them because even a very short power disturbance can scrap wafers in process, and a stop of safety systems could lead to an accident.

Also called: UPS

Diagram


What an uninterruptible power supply protects in a semiconductor fab

Click anywhere to zoom in there. Scroll to zoom, drag to move

Large fabs may use high-capacity systems that protect a whole building.

Why voltage sags matter in a fab


Complete outages are rare; short voltage sags, often caused by lightning on the grid and lasting from tens of milliseconds to a few seconds, are more common. If a tool's controller, a vacuum pump or an RF generator drops out even briefly, the wafers being processed may go out of specification and be scrapped, and restarting and requalifying the tool takes time.

Fabs therefore put UPS protection on tool control systems, on safety systems such as toxic gas monitoring, exhaust and abatement, and on production computers such as MES servers. For large loads across the fab, voltage sag compensators or flywheel-based systems cover the brief dip.

UPS types and tool ride-through


An online (double-conversion) UPS always supplies power through its inverter, so there is no switchover when the mains fails and disturbances do not reach the load. It is used for critical systems. Standby or line-interactive types pass mains power through normally and switch to battery on a fault; they are more efficient and cheaper.

Tools themselves are also expected to ride through sags. The SEMI F47 standard specifies voltage sags of set depth and duration that equipment must withstand without stopping. Together, facility protection and tool immunity limit losses from power disturbances.

Japanese companies involved


  • Fuji Electric and Mitsubishi Electric make large UPS systems for industrial and data centre use, alongside their power semiconductor businesses.

FAQ


What is SEMI F47?

A SEMI standard for voltage sag immunity of semiconductor equipment. It defines dips of given depth and duration that a tool must ride through without stopping, so that short grid disturbances do not interrupt processing.

Does a fab put the whole factory on UPS?

Usually not. Large loads such as chillers and air handling are too big to back up with batteries economically. Fabs protect critical controls and safety systems with UPS and use sag compensation or other systems for larger loads.